What Size Wire for 80 Amps?

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 12, 2026.

Use 4 AWG copper for an 80 amp breaker, or 2 AWG aluminum. For NM-B (Romex) cable the minimum is 3 AWG copper. Long runs may need a size larger, as the voltage drop table below shows.

Wire size for an 80 amp breaker

WireConditionMinimum size for 80 A
CopperNM-B (Romex) cable or 60°C terminals3 AWG
CopperTHHN/THWN in conduit, 75°C terminals4 AWG
Aluminum75°C terminals2 AWG
Aluminum60°C terminals1 AWG

4 AWG copper is rated 70 A in the 60°C column, 85 A at 75°C and 95 A at 90°C. The size above is the smallest whose ampacity is at least 80 A. Most modern breakers and panels have 75°C terminals, but an 80 A circuit is presumed 60°C unless the equipment is marked otherwise (NEC 110.14(C)).

Voltage drop: how far can 4 AWG run at 80 A?

The 4 AWG above carries 80 A safely but loses voltage over distance. At the full 80 A and 240 V, 4 AWG copper stays within the NEC's 3% recommendation for about 146 ft one way. 3 AWG stretches that to 184 ft.

One-way distance4 AWG copper3 AWG copper2 AWG copper
25 ft0.5%0.4%0.3%
50 ft1.0%0.8%0.6%
100 ft2.1%1.6%1.3%
150 ft3.1%2.5%1.9%
200 ft4.1%3.3%2.6%

Percent drop at 80 A and 240 V.

On 120 V circuits, the 80 A percentages are twice these values.

Check your own 80 A run with the voltage drop calculator, or let the wire size calculator choose the size for you.

What an 80 amp circuit is used for

Cable type matters

NM-B for an 80 A circuit has to be 3 AWG, because 4 AWG NM-B tops out at 70 A. In conduit, 4 AWG THHN is rated 85 A at 75°C and covers an 80 A breaker.

Continuous loads and common mistakes

On an 80 A breaker, a continuous load running three hours or more should not exceed 80% of the rating. That is 64 A, or about 15,360 W at 240 V. The difference between 3 AWG and 4 AWG is the cable type. Pick the wire for how it is installed, and check that the terminals are rated 75°C if you want the smaller size.

For an 80 A breaker the ground wire comes from NEC Table 250.122. Use the ground wire size calculator. For other breaker sizes, see the breaker to wire size chart, or jump to 20 amps, 30 amps, 40 amps, 50 amps, 60 amps, 100 amps.

Frequently asked questions

What size wire for an 80 amp breaker?

4 AWG copper at 75°C terminals, or 3 AWG for NM-B cable. In aluminum use 2 AWG.

How far can 4 AWG wire run on 80 amps?

About 146 feet one way at 240 V before the voltage drop passes the NEC's 3% recommendation. Past that distance, step up to 3 AWG.

What size wire for an 80 amp breaker?

4 AWG copper in conduit with 75°C terminals, or 3 AWG for NM-B cable. In aluminum use 3 AWG at 75°C.

What size wire for an 80 amp sub panel?

4 AWG copper in conduit, or 3 AWG cable. For long runs, step up for voltage drop.