What Size Wire for 150 Amps (and 125 Amps)?

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 12, 2026.

For a 150 amp feeder use 1/0 AWG copper or 3/0 AWG aluminum. For 125 amps use 1 AWG copper or 2/0 AWG aluminum. These are 75°C sizes, which is the column you use above 100 amps.

Wire size for a 125 and 150 amp feeder

BreakerCopper, 75°CAluminum, 75°CGround wire (Cu / Al)
125 A1 AWG2/0 AWG6 AWG / 4 AWG
150 A1/0 AWG3/0 AWG6 AWG / 4 AWG

Above 100 A you use the 75°C column of NEC Table 310.16. That is why the copper size is 1 AWG for 125 A (130 A in the table) and 1/0 AWG for 150 A (150 A in the table). The ground comes from NEC Table 250.122, which gives 6 AWG copper or 4 AWG aluminum for any breaker from 101 to 200 A.

Not the same as a service

If you are feeding a whole house from the utility, NEC 310.12 lets a single-family dwelling use smaller conductors, and the 200 amp service page has that table. That shortcut is for the service or main feeder that carries the whole load of a home. A sub panel in a detached garage or barn uses the sizes above.

How far can it run?

These are the longest one-way runs within 3% voltage drop at the full rated current on 240 V.

WireAt 125 AAt 150 A
1 AWG copper187 ft156 ft
1/0 AWG copper236 ft196 ft
2/0 AWG copper297 ft248 ft
1/0 AWG aluminum143 ft120 ft
2/0 AWG aluminum181 ft151 ft
3/0 AWG aluminum228 ft190 ft

Most feeders do not run at their full rating all day, so the real drop is lower. Put your own distance into the voltage drop calculator if you're close to the limit.

Get a permit. A feeder this size usually needs a permit and an inspection. Conduit size, a main disconnect at the detached building and the grounding rules all vary by location, so confirm the details with your inspector or a licensed electrician.

For other breaker sizes, see the breaker to wire size chart.

Frequently asked questions

What size wire for a 150 amp breaker?

1/0 AWG copper or 3/0 AWG aluminum at 75°C.

What size wire for a 125 amp breaker?

1 AWG copper or 2/0 AWG aluminum at 75°C.

What size ground wire for a 150 amp sub panel?

6 AWG copper or 4 AWG aluminum, from NEC Table 250.122.

Can I use 2 AWG for a 125 amp breaker?

Not as a regular feeder. 2 AWG copper is rated 115 A at 75°C, which is under 125 A.

Sources