4 Gauge Wire: How Many Amps Can It Handle?

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 12, 2026.

4 gauge copper wire is rated 70 amps at 60°C, 85 amps at 75°C and 95 amps at 90°C. The table below shows how far it can run at each voltage before the voltage drop passes 3%.

4 gauge wire at a glance

Diameter (bare copper)0.2043 in (5.19 mm)
Cross-section area21.15 mm² (41,740 circular mils)
Copper ampacity, 60°C / 75°C / 90°C70 / 85 / 95 A
Maximum breaker (copper)80 A
Aluminum ampacity, 60°C / 75°C / 90°C55 / 65 / 75 A

14 AWG copper is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A, and 12 and 10 AWG aluminum to 15 A and 25 A, by the overcurrent rules in NEC 240.4(D), even where the ampacity table lists more.

How far can 4 gauge wire run?

Current is only half the story. The wire loses voltage over distance, and the NEC recommends staying within 3%. This table gives the longest one-way run of 4 AWG copper within 3% drop, by current and voltage.

Current12 V DC24 V DC120 V AC240 V AC
40 A15 ft29 ft146 ft291 ft
70 A8.3 ft17 ft83 ft166 ft
85 A6.9 ft14 ft69 ft137 ft

Use the voltage drop calculator for another size, current or limit. For 12 V runs by size, see the 12V wire gauge chart.

What 4 gauge wire is used for

Cable type and the rules

4/3 NM-B (Romex) is rated 70 A. In conduit, 4 AWG THHN is rated 85 A at 75°C. The 100 A dwelling service use is a special case and only applies to a main service or feeder, not a sub panel.

Neighboring sizes

GaugeDiameterCopper amps (75°C, with NEC 240.4(D) limits)
6 AWG0.1620 in65 A
4 AWG0.2043 in85 A
3 AWG0.2294 in100 A

The wire gauge chart covers every size, and the amps per wire size table lists them in all three temperature columns.

Frequently asked questions

How many amps can 4 gauge wire handle?

70 amps at 60°C, 85 amps at 75°C and 95 amps at 90°C for copper.

What size breaker for 4 gauge wire?

A 70 amp breaker for NM-B cable, or 80 amps in conduit on 75°C terminals.

How far can 4 gauge wire run at 240 volts?

About 166 feet one way at 70 A within 3% drop.

Can 4 gauge wire be used for a 100 amp panel?

Only as a single-family dwelling service or main feeder under NEC 310.12. For a sub panel use 3 AWG copper.