14 Gauge Wire: How Many Amps Can It Handle?

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

14 gauge copper wire carries 15 amps in building wiring. The NEC table lists 15 A at 60°C, 20 A at 75°C and 25 A at 90°C, but NEC 240.4(D) caps the breaker at 15 A. The table below shows how far it can run at each voltage before the voltage drop passes 3%.

14 gauge wire at a glance

Diameter (bare copper)0.0641 in (1.63 mm)
Cross-section area2.08 mm² (4,110 circular mils)
Copper ampacity, 60°C / 75°C / 90°C15 / 20 / 25 A
Maximum breaker (copper)15 A
AluminumNot used

14 AWG copper is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A, and 12 and 10 AWG aluminum to 15 A and 25 A, by the overcurrent rules in NEC 240.4(D), even where the ampacity table lists more.

How far can 14 gauge wire run?

Current is only half the story. The wire loses voltage over distance, and the NEC recommends staying within 3%. This table gives the longest one-way run of 14 AWG copper within 3% drop, by current and voltage.

Current12 V DC24 V DC120 V AC240 V AC
5 A11 ft23 ft115 ft229 ft
10 A5.7 ft11 ft57 ft115 ft
15 A3.8 ft7.6 ft38 ft76 ft

Use the voltage drop calculator for another size, current or limit. For 12 V runs by size, see the 12V wire gauge chart.

What 14 gauge wire is used for

Cable type and the rules

14/2 NM-B (Romex) is the standard cable for 15 A lighting circuits. It cannot be used on a 20 A circuit. If the circuit has a 20 A breaker, every wire on it must be 12 AWG.

Neighboring sizes

GaugeDiameterCopper amps (75°C, with NEC 240.4(D) limits)
14 AWG0.0641 in15 A
12 AWG0.0808 in20 A

The wire gauge chart covers every size, and the amps per wire size table lists them in all three temperature columns.

Frequently asked questions

How many amps can 14 gauge wire handle?

15 amps. The 75°C column shows 20 A, but NEC 240.4(D) limits 14 AWG copper to a 15 A breaker.

Can I use 14 gauge wire for a 20 amp circuit?

No. Use 12 AWG for a 20 amp circuit.

How far can 14 gauge wire run at 120 volts?

About 38 feet one way at the full 15 A within 3% voltage drop, and much farther at lower current. At 7.5 A it is about 76 feet.

Is 14 gauge wire OK for 12 volt DC?

Only for short runs or low current. At 12 V and 10 A the limit is about 6 feet one way for 3% drop, since DC at low voltage loses a large share of the voltage.

Sources